| TESTING FOR ACIDIC "Refrigerant Gas" |
|
| Reaction: | BLUE
Positive test will yield yellow and/or white crystals. |
| Sensitivity: | 0.10 ppm (0.00001%). |
| Accuracy: | |
| Standard: | ARI recommends that the total acid content be less than 1.0 ppm for refrigerant gas. (Midpoint of detector tube scale). |
| False Reactions: | NONE. |
| Correlations: | The acid present in the oil is not directly indicated. If the test is negative, the system oil may be neutral to slightly acidic. If the tube registers 'any' acid reading, the oil is usually "highly acidic". |
![]()
| MOISTURE ANALYSIS "Refrigerant Gas" |
|
| Reaction: | LT.
BROWN OR PINK
|
| Sensitivity: | 1.0 ppm (0.0001%). |
| Accuracy: | |
| Standard: | ARI has established a 10 ppm limit for reusable refrigerant. |
| False Reactions: | From atmospheric moisture. Be sure to purge extension hose and the metering body inlet fitting with the refrigerant gas being tested. Highly acidic refrigerant gas voids the test. |
| Correlations: | The amount of moisture present in the oil can be 5 to 10 times greater. |